STEAM TRAPS & PIPELINE ACCESSORIES

Thermodynamic Steam Trap

WORKING PRINCIPLE

Thermodynamic steam trap operates on the principle of thermodynamic and fluid dynamics. They utilise the heat energy of hot condensate and the kinetic energy in the steam to open and close.

FEATURES
  • Thermodynamic steam trap is complete stainless steel internals ensure better mechanical & corrosion resistance properties.
  • Condensate entry below the disc, concentric to the disc/seat ensures a clean & parallel lift of the disc with reference to the seat, eliminating localized wear & tear.
  • The disc & seat are fully hardened by a special hardening process, to withstand continuous, prolonged operation.
  • Perfect shut off, no steam loss.
  • Thermodynamic steam trap is robust, maintenance free, fully guaranteed.

INSTALLATION

Thermodynamic steam trap will operate in any position but the preferred installation is in a horizontal position with the disc seat cover on top. Full port isolating valves should be installed upstream and downstream of the trap.

MAINTENANCE

  • Thermodynamic steam trap can be maintained without disturbing the piping connections. Ensure that the trap is isolated – upstream and downstream – before attempting to dismantle it. ALLOW THE TRAP TO COOL BEFORE DISMANTLING.
  • For trouble-free performance, periodic cleaning of the disc, seat and strainer screen is recommended.
  • Do not use abrasive/corrosive media for cleaning. Only the disc and seat are subject to wear. A worn disc can be replaced. Slight seat wear can often be corrected by resurfacing on a lap plate.
AVAILABLE SPARES
  • Disc
  • Strainer Screen
  • Blow Down Valve
  • Isotub
  • Set of gaskets
APPLICATION
  • Header
  • Main line drains
  • Drip legs
  • High pressure line drains
ADVANTAGES
  • Thermodynamic steam trap is Simple, small and light construction
  • It can be mounted in any position
  • Thermodynamic steam trap is Rugged, not affected by water hammer
  • Operate over a wide pressure range
  • Follow the steam saturation curve
  • Performance of thermodynamic steam trap easy to check
  • Primary failure mode – open
IMPORTANT NOTE
  • Thermodynamic steam trap should be installed as close as possible to the line to be drained.
  • For new pipelines, ensure that the lines are properly flushed, prior to fitting the traps to avoid strainer choke-up.

PRODUCT RANGE (Thermodynamic Steam Trap):

Model Size Material End Connections PMA Bar/
TMA (°C)
Cap.at
PMO (Kg/hr)
PT10 DN15,20 A743 Gr. CA40 Screwed (NPT / BSPT / BSP), SW, FL 21/426 440
PT11 DN15,20,25 A743 Gr. CA40 Screwed (NPT / BSPT / BSP), SW, FL 42/426 727 / 1066
PT11H DN15,20,25 A743 Gr. CA40 Screwed (NPT / BSPT / BSP), SW, FL 42/426 2280 / 2880
PT13 DN15,20 Repairable A217 Gr. WC6 SW, FL 65/510 590
PT14 DN15,20,25 Repairable A182 Gr.
F22 Cl. 3
SW, FL, BW #1500
200/300
620
PT16 DN 8, 10, 15, 20, 25 A743 Gr. CA40 Screwed (NPT / BSPT / BSP), SW 42/426 759 / 1135
PT17R DN15,20,25 Repairable A105 Screwed (NPT / BSPT / BSP), SW, BW, FL 50/426 675 / 1080
PT18 DN15,20 A743 Gr. CA40 Suitable for universal connector 42/426 850
PT18Y DN15,20 A743 Gr. CA40 Suitable for universal connector 42/426 850

PT10

Thermodynamic Steam Trap with inbuilt strainer, SS construction: A743 Gr. CA40. End conns.: Screwed NPT/BSPT/BSP/SW/FL

Imperial

PMA TMA PMO TMO Maximum Capacity (lbs/hr) Size
300 psig @ 38 degF 800 degF #150, #300 600 psig @ all operating temperatures 980 ½”, ¾”

Metric

PMO (bar) TMA (ºC) Capacity at PMO (kg/hr) Size
21 / 426 440 DN15, 20

PT11

Thermodynamic Steam Trap with inbuilt strainer, SS construction: A743 Gr. CA40. End conns.: Screwed NPT/BSPT/BSP/SW/FL

Imperial

PMA TMA PMO TMO Maximum Capacity (lbs/hr) Size
600 psig @ 38 degF 800 degF #150, #300 600 psig @ all operating temperatures 1600 2350 ½”, ¾” 1”

Metric

PMO (bar) TMA (ºC) Capacity at PMO (kg/hr) Size
42 / 426 725 1066 DN15, 20 DN25

PT11H

High capacity Thermodynamic Steam Trap with inbuilt strainer, SS construction:A743 Gr. CA40. End conns.: Screwed NPT/BSPT/BSP/SW/FL

Imperial

PMA TMA PMO TMO Maximum Capacity (lbs/hr) Size
600 psig @ 38 degF 800 degF #150, #300 600 psig @ all operating temperatures 5100 6440 ½”, ¾” 1”

Metric

PMO (bar) TMA (ºC) Capacity at PMO (kg/hr) Size
42 / 426 2280 2880 DN15,20 DN25

PT13

Thermodynamic Steam Trap with inbuilt strainer. Alloy Steel body. SS internals. End conns.: SW/FL

Imperial

PMA TMA PMO TMO Maximum Capacity (lbs/hr) Size
925 psig @ 38 degF 950 degF 925 psig @ all operating temperatures 950 degF 5100 6440 ½”, ¾”

Metric

PMO (bar) TMA (ºC) Capacity at PMO (kg/hr) Size
65 / 510 590 DN15, 20

PT14N

Thermodynamic Steam Trap with inbuilt strainer. Forged Alloy Steel body, SS internals, End conns. SW / BW

Imperial

PMA TMA PMO TMO Maximum Capacity (lbs/hr) Size
3550 psig @ 38 degF 1000
degF
3500 psig @ all operating temperatures 1000
degF
1365 ½” ~ 1

Metric

PMO (bar) TMA (ºC) Capacity at PMO (kg/hr) Size
175 / 537 630 DN15~25

PT16

Thermodynamic Steam Trap. SS construction, A743 Gr. CA40. End conns.: Screwed NPT / BSPT / BSP / SW

Imperial

PMA TMA PMO TMO Maximum Capacity (lbs/hr) Size
600 psig @ 38 degF 800 degF 600 psig @ all operating temperatures 800
degF
1670 2500 ¼” ~ ¾” 1”

Metric

PMO (bar) TMA (ºC) Capacity at PMO (kg/hr) Size
42 / 426 759 1135 DN8~20 DN25

PT17R

Thermodynamic Steam Trap with inbuilt strainer, Forged Carbon Steel body, SS internals, End conns.: Screwed NPT / BSPT / SW / BW / Flanged

Imperial

PMA TMA PMO TMO Maximum Capacity (lbs/hr) Size
710 psig @ 38 degF 800 degF 710 psig @ all operating temperatures 800
degF
1615 2545 ½”, ¾” 1”

Metric

PMO (bar) TMA (ºC) Capacity at PMO (kg/hr) Size
50 / 426 735 1138 DN15, 20 DN25

PT18

Thermodynamic Steam Trap for Universal Connector SS construction, A743 Gr CA40. (To be used with Universal connector – PU11 / PU11Y)

Imperial

PMA TMA PMO TMO Maximum Capacity (lbs/hr)
600 psig @ 38 degF 800 degF 600 psig @ all operating temperatures 800
degF
1870

Metric

PMO (bar) TMA (ºC) Capacity at PMO (kg/hr) Size
42 / 426 850 DN15, 20