FLOW CONTROL PRODUCTS

PD61 / PAE61

Ball Float Steam Traps-pt61

Ball float steam traps works on density principle. Ball float traps senses the density difference between steam and condensate. Condensate entering the steam trap causes the ball float to rise and makes valve to lift off its seat and releases the condensate entering the steam trap. As the condensate in trap

Features of Pennant control valve
  1. Pennant ball float steam traps comes with air vent which allows the air to pass out of the steam trap.
  2. Float type steam traps also comes with Steam Lock Release (SLR) unit, which can be used to avoid steam locking/flooding condition inside steam trap.
  3. Can handle heavy condensate loads.
  4. Can be customized as per customer requirements.
  5. Float type steam traps can offer higher heat transfer rate, discharges condensate at steam temperature.
  6. Pennant ball float steam traps can easily handle water hammer and sudden fluctuations in pressure and flow rate.

INSTALLATION

  • Ball float steam trap-PT 61-Standard horizontal installation with flow from right to left.
  • Upon request we can provide our ball float traps with following installations as well

AVAILABLE SPARES:

Valve Seat, Ball Float & Lever Assembly, Air Vent Assembly. Gaskets.

Typical Applications of Ball float steam traps:-

  • Heating coils
  • Hot water heaters
  • Steam separators
  • Reactors
  • Sterilizers
  • Autoclaves
  • Dryers
  • Dehumidifiers 
  • Heat exchangers
Available Types:
  • PT61 – with Thermostatic Air Vent 
  • PT61S – with Steam Lock Release (SLR) 
  • PT61C – with Thermostatic Air Vent & SLR
Sizes

DN 15, 20, 25

Available Spares

Valve Seat, Ball Float & Lever Assembly,
Air Vent Assembly.
Gaskets.

Max. Differential Pressure Range:
  • PT61-4.5 : 4.5 bar 
  • PT61-10 : 10 bar
  •  PT61-14 : 14 bar

INSTALLATION

  • Ball float steam trap-PT 61-Standard horizontal installation with flow from right to left.
  • Upon request we can provide our ball float traps with following installations as well
  1. Horizontal installation with flow from left to right PT61 (L-R) 
  2. Vertical installation with flow from   top to bottom PT61(V)

The Ball float steam trap should be installed below the drain point of the equipment in a position so that the float arm is in a horizontal plane and the float rises and falls vertically, with the flow direction as indicated on the body. The arrow on the nameplate should be pointing vertically upwards.

CONNECTIONS

Screwed (NPT/BSPT/BSP)

Limiting Conditions:

PMA: Max. allowable pressure 250 psig
TMA: Max. allowable temperature 425 °F
PMO: Max. operating pressure 200 psig
TMO: Max. operating temperature 425 °F
Cold hydro test pressure 375 psig

MATERIAL

NO. PART MATERIAL
1 BODY CAST IRON IS : 210 FG20
2 COVER
3 GASKET (COVER) Non CAF
4 VALVE SEAT AISI 410/ AISI
5 VALVE
6 LEVER AISI 304
7 FLOAT AISI 304
8 AIR VENT ASSLY. AISI 304
9 BOLT HIGH TENSILE
10 DRAIN PLUG C.S
11 GASKET DRAIN PLUG COPPER
12 GASKET AIR VENT COPPER
13 GASKET VALVE SEAT COPPER
14 BRACKET ASSLY. AISI 304
15 LABEL AISI 304

*Only for 1″ size (Not shown in view)

Imperial

PMA TMA PMO TMO Maximum Capacity (lbs/hr) Size
250 psig 425 °F 200 psig 425 °F 1090 2706 ½”,¾”, 1”

Metric

PMO (bar) TMA (ºC) Capacity at PMO (kg/hr) Size
14 / 220 482 510 DN15, 20 DN25